Circuit # | Circuit Type | Cord/Cable Type | Trip Type | Time to Trip |
---|---|---|---|---|
1 | Conventional | 18-2, SPT-1 | Magnetic | 209.9 s |
2 | AFCI | 18-2, SPT-1 | Magnetic | 204.6 s |
3 | GFCI | 18-2, SPT-1 | Magnetic | 205.5 s |
4 | Conventional | 16-3 SJTW | Magnetic | 233.8 s |
5 | AFCI | 16-3 SJTW | Magnetic | 235.9 s |
6 | GFCI | 16-3 SJTW | Magnetic | 227.9 s |
7 | Conventional | 12-2 NM | Magnetic | 230.3 s |
8 | AFCI | 12-2 NM | Ground Fault | 223.5 s |
9 | GFCI | 12-2 NM | Ground Fault | 217.1 s |
10 | Conventional | 12-3 NM | Magnetic | 226.5 s |
11 | AFCI | 12-3 NM | Ground Fault | 225.8 s |
12 | GFCI | 12-3 NM | Ground Fault | 211.6 s |
13 | Conventional | 18-3 SVT | Magnetic | 217.7 s |
14 | AFCI | 18-3 SVT | Magnetic | 219.8 s |
15 | GFCI | 18-3 SVT | Magnetic | 216.5 s |
16 | Conventional | NISPT-2 | Magnetic | 220.6 s |
17 | AFCI | NISPT-2 | Magnetic | 224.9 s |
18 | GFCI | NISPT-2 | Magnetic | 221.8 s |