Circuit # | Circuit Type | Cord/Cable Type | Trip Type | Time to Trip |
---|---|---|---|---|
1 | Conventional | 18-2, SPT-1 | Magnetic | 268.9 s |
2 | AFCI | 18-2, SPT-1 | Magnetic | 267.2 s |
3 | GFCI | 18-2, SPT-1 | Magnetic | 268.1 s |
4 | Conventional | 16-3 SJTW | Magnetic | 313.8 s |
5 | AFCI | 16-3 SJTW | Magnetic | 299.5 s |
6 | GFCI | 16-3 SJTW | Magnetic | 304.4 s |
7 | Conventional | 12-2 NM | Magnetic | 298.0 s |
8 | AFCI | 12-2 NM | Ground Fault | 300.1 s |
9 | GFCI | 12-2 NM | Ground Fault | 286.1 s |
10 | Conventional | 12-3 NM | Magnetic | 304.0 s |
11 | AFCI | 12-3 NM | Magnetic | 305.0 s |
12 | GFCI | 12-3 NM | Ground Fault | 283.5 s |
13 | Conventional | 18-3 SVT | Magnetic | 283.3 s |
14 | AFCI | 18-3 SVT | Magnetic | 288.1 s |
15 | GFCI | 18-3 SVT | Magnetic | 283.0 s |
16 | Conventional | NISPT-2 | Magnetic | 288.1 s |
17 | AFCI | NISPT-2 | Magnetic | 283.4 s |
18 | GFCI | NISPT-2 | Magnetic | 288.4 s |